Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 06/12/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The service is not per code.| 210* 1. GROUND RODS MUST BE DRIVEN TO A DEPTH OF 8' AND DO NOT BEND RODS - NEC 250.53 2. BOND GAS AND WATER PIPES TO SERVICE NEC 250.104 3. COMPLETE POLE RISER 4. TIGHTEN LOCKNUT FOR SERVICE RISER. |