Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2006 | ELECTRIC - FINAL | Denied | 1. AC UNIT ON GROUND CANNOT BE IN FRONT OF SERVICE 2002 NEC 110-26 MUST HAVE CLEARANCE IN FRONT OF TO GRADE. 2. GROUND WIRE IN 8X8 J-BOX ABOVE SERVICE TO BE ATTACHED TO J-BOX. 3. UF WIRE TO SIDE OF SERVICE TO BE RUN IN CONDUIT. |