Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/03/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY TERMINATE EQUIPMENT GROUNDS IN J-BOX AND GROUND ENCLOSURE. 2. IDENTIFY BRANCH CKTS CORRECTLY 3. MAX 15. AMP BREAKER ON 14 GA WIRE 4. IDENTIFY NEUTRALS WITH WHITE TAPE. 5. CLEAN UP ALL WIRING (MAKE NEAT) AND REMOVE OLD WHITE BOND WIRE. 6. MOUNT EXTERIOR J-BOX TO WALL SURFACE. |
|
| 06/13/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 06/02/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. SECURE GROUND TO STRUCTURE. 2. FINISH WORK TO CROSS OVER STAGE. |