Permit: T06EL00954

Parcel: 119040620


Addresses:

3662 S LUNDY AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/26/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) CALL FOR FINAL ONCE CHANGED OVER
05/24/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO INSTALL SERVICE ENTRANCE IN RISER ONE NEEDS TO BE TAPED WHITE AT BOTH ENDS.
2. RISER BELOW ROOF NEEDS 2 STRAPS ONE WITHIN 3' OF SERVICE.
3. USE A ROMEX CLAMP ON GROUND WIRES & STRAP GROUND WIRES TO WALL.
4. DRIVE GROUND RODS TO GRADE OR BELOW
5. BOND GAS LINE (AT WATER LINE OR HEATER)
6. LEAVE 2' OF WIRE OUT OF WEATHERHEAD FOR TEP