Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDED CONDUCTOR TO BE CORRECTLY IDENTIFIED 2) PREVIOUS ITEMS CORRECTED |
|
| 11/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT ENTER AT TOP OR PASS THROUGH METER SECTION PER MANUFACTURE. 2. GROUND JUNCTION BOX. 3. TIGHTEN LOOSE FITTINGS. 4. SPACE CONDUCTOR TO BE SAME SIZE AS ORIGINAL CONDUCTOR AND SAME COLOR. 5. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8 6. GAS BOND TO BE TO INTERIOR SIDE PIPING. 7. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 8. SERVICE GROUNDING ELECTRODE CONDUCTOR WITH APPROVED MEANS. |
|
| 11/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE ELECTRICIAN ON SITE FOR INSPECTION. |