Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/19/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SMOKE DETECTORS REQUIRED IN BEDROOMS - BATTERY 2. EXPOSED ROMEX BELOW 8' IN CLOSET AND IMPROPERLY RUN TO LIGHT WITH NO BOX BEHIND IT (SOUTH CLOSET). 3. NORTH CLOSET -- WIRE RUN DIRECTLY TO FIXTURE - NEEDS BOX 4. KITCHEN RECEPTACLE TO BE GFI PROTECTED. 5. STORAGE ROOMS & LAUNDRY ALL EXPOSED WIRING BELOW 8' TO BE PHYSICALLY PROTECTED. |
|
| 05/18/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* FRI 9:30 AM SOMEONE THERE FROM VAIL |