Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #9 PEDESTAL OUTSIDE UNIT, PARK: MOBILE CORD ENTERS THRU OPEN HOLE MUST HAVE CLAMP. -SEAL OTHER OPEN HOLE - NEUTRAL FROM SERVICEONLY HALF TERMINATED. - REMOVE SPLICES ON CORD AN TIE DIRECTLY INTO BREAKER. - REMOVE 50 AMP. FEED TO #12 CORD. (PEDESTAL DISCONNECT NEEDS TO BE REDONE BY AN ELECTRICIAN. OWNER: INSIDE PNL - REMOVE GE BREAKER USE SQ D - PROTECT WIRING ON BACK SIDE OF ENCLOSURE WHERE WIRING ENTERS. |