Permit: T06EL00936

Parcel: 110030890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00936

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#9 PEDESTAL OUTSIDE UNIT,
PARK:
MOBILE CORD ENTERS THRU OPEN HOLE MUST HAVE CLAMP.
-SEAL OTHER OPEN HOLE
- NEUTRAL FROM SERVICEONLY HALF TERMINATED.
- REMOVE SPLICES ON CORD AN TIE DIRECTLY INTO BREAKER.
- REMOVE 50 AMP. FEED TO #12 CORD.
(PEDESTAL DISCONNECT NEEDS TO BE REDONE BY AN ELECTRICIAN.
OWNER: INSIDE PNL - REMOVE GE BREAKER USE SQ D
- PROTECT WIRING ON BACK SIDE OF ENCLOSURE WHERE WIRING ENTERS.