Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE ROOF FLASHING FOR MAST. 2. PROVIDE GUY SUPPORT FOR MAST. 3. CONDUCTORS ENTERING PANEL NEED BUSHING OR CONNECTOR. 4. INSTALL GROUND RODS FOR SERVICE. 5. BOND GAS PIPE TO SERVICE. 6. REMOVE TEMPORARY WIRING FROM NEIGHBORS HOUSE IT CREATES A HAZARD. |
|
| 05/22/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSTALL SERVICE CONDUCTORS AND WEATHERHEAD BEFORE INSPECTION. |