Permit: T06EL00923

Parcel: 107140340

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
BOND GAS & WA, REMOVE PAINT, NO SOFT TOP SCREWS, BURY GROUND WIRE 2ND RD?
10/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND BOTH GAS & WATER PIPES & USE PROPER SIZE CLAMPS, REMOVE PAINT.
2. SELF TAP SCREWS NOT ALLOWED FOR GROUND BARS.
3. BURY GROUNDING ELECTRODE CONDUCTOR 12" OR SECURE TO STRUCTURE, CAN'T FIND 2ND GROUND ROD.