Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* BOND GAS & WA, REMOVE PAINT, NO SOFT TOP SCREWS, BURY GROUND WIRE 2ND RD? |
|
| 10/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND BOTH GAS & WATER PIPES & USE PROPER SIZE CLAMPS, REMOVE PAINT. 2. SELF TAP SCREWS NOT ALLOWED FOR GROUND BARS. 3. BURY GROUNDING ELECTRODE CONDUCTOR 12" OR SECURE TO STRUCTURE, CAN'T FIND 2ND GROUND ROD. |