Permit: T06EL00917

Parcel: 125041310


Addresses:

1022 N OLSEN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
GATE IS LOCKED.
05/25/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
* INSTALL ROOF JACK AT RISER.
* DRIVE RODS FLUSH OR BELOW FINISHED GRADE (BURY GROUNDING ELECTRODE CONDUCTOR).
* INSULATION ON EXPOSED RISER CONDUCTORS MUST BE SUNLIGHT RESISTANT.
* ARRANGE ACCESS TO FOLLOW THE NEW CONDUCTORS BETWEEN THE SERVICE PANEL & INTERIOR CONNECTION PROVIDE LADDER IF NECESSARY.
YOUR WORK LOOKS GOOD TAKE CARE OF THE ABOVE ITEMS AND RESCHEDULE AT 740-6970 -- THANKS BOB