Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* GATE IS LOCKED. |
|
| 05/25/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* * INSTALL ROOF JACK AT RISER. * DRIVE RODS FLUSH OR BELOW FINISHED GRADE (BURY GROUNDING ELECTRODE CONDUCTOR). * INSULATION ON EXPOSED RISER CONDUCTORS MUST BE SUNLIGHT RESISTANT. * ARRANGE ACCESS TO FOLLOW THE NEW CONDUCTORS BETWEEN THE SERVICE PANEL & INTERIOR CONNECTION PROVIDE LADDER IF NECESSARY. YOUR WORK LOOKS GOOD TAKE CARE OF THE ABOVE ITEMS AND RESCHEDULE AT 740-6970 -- THANKS BOB |