Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00915
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEAL TIGHT FROM DISCONNECTS TO BLOWERS NEED TO BE SECURED AND ARRANGED SO THEY DO NOT BLOCK ENTRANCE ALL FOUR DISCONNECTS. 2. PIGTAIL GROUND SO YOU DO NOT HAVE TWO STRANDED UNDER SAME GROUND LUG. 3. PROVIDE DRAWING (APPROVED) AND SEALED LETTER DETAILING MODIFICATION TO STRUCTURE BRACE IN FRONT OF PANELS (FROM ENGINEER). |
|
06/20/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANELS "D" & "E" AND TRANSFORMER FOR "E" NEED PROPER WORKING CLEARANCE PROVIDED IN NEC 110.26 2. BONDING JUMPER FOR TRANSFORMER IS UNDERSIZED AND MUST CONNECT UNDER THE SAME LOCATION AS GROUNDING ELECTRODE CONDUCTOR (NEC 250.30(A)(1) AND NEC 250.30(A)(2) 3. DO NOT INSTALL CONDUCTORS OF DIFFERENT SIZES UNDER SAME LUG UNLESS LUG IS LISTED FOR THAT NEC 110. 4. SECURE TRANSFORMER TO FLOOR NEC 110.13(A) 5. FINISH WIRING TO EXTERIOR COOLERS NEC 430.101 *NOTE: IF CROSS BEAM IS REMOVED A LETTER FROM ENGINEER (SEALED) MUST BE PROVIDED. |