Permit: T06EL00915

Parcel: 103090310


Addresses:

2025 W HIGHWAY DR


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00915

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SEAL TIGHT FROM DISCONNECTS TO BLOWERS NEED TO BE SECURED AND ARRANGED SO THEY DO NOT BLOCK ENTRANCE ALL FOUR DISCONNECTS.
2. PIGTAIL GROUND SO YOU DO NOT HAVE TWO STRANDED UNDER SAME GROUND LUG.
3. PROVIDE DRAWING (APPROVED) AND SEALED LETTER DETAILING MODIFICATION TO STRUCTURE BRACE IN FRONT OF PANELS (FROM ENGINEER).
06/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANELS "D" & "E" AND TRANSFORMER FOR "E" NEED PROPER WORKING CLEARANCE PROVIDED IN NEC 110.26
2. BONDING JUMPER FOR TRANSFORMER IS UNDERSIZED AND MUST CONNECT UNDER THE SAME LOCATION AS GROUNDING ELECTRODE CONDUCTOR (NEC 250.30(A)(1) AND
NEC 250.30(A)(2)
3. DO NOT INSTALL CONDUCTORS OF DIFFERENT SIZES UNDER SAME LUG UNLESS LUG IS LISTED FOR THAT NEC 110.
4. SECURE TRANSFORMER TO FLOOR NEC 110.13(A)
5. FINISH WIRING TO EXTERIOR COOLERS NEC 430.101
*NOTE: IF CROSS BEAM IS REMOVED A LETTER FROM ENGINEER (SEALED) MUST BE PROVIDED.