Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1. ADDRESS SERVICE 2. MOVE WHITE TAPE ON NEUTRAL TO 6" OUT OF WEATHERHEAD 3. MAKE SURE TO REBOND WATER & GAS ONCE SERVICE IS CHANGED OVER. 4. CLAMPS ON RODS TO BE BRASS & BRASS SCREWS CALL ONCE CHANGED OVER. |