Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORY NEEDS TO BE IDENTIFIED CORRECTLY AND LEGIBLY NEC 408.4 2. GROUNDING ELECTRODE CONDUCTOR NOT ALLOWED IN EMT UNLESS MADE ELECTRICALLY CONTINUOUS NEC 250.64(E) EMT IS ALSO A TRIPPING HAZARD. |
|
| 05/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE INHIBITOR ON ALUMINUM CONNECTIONS. 2. PANEL DIRECTORY NOT MARKED CORRECTLY. 3. IDENTIFY WHITE CONDUCTOR USED AS HOT 4. SECURE GROUNDING ELECTRODE CONDUCTOR (G.E.C) ACROSS SIDEWALK SO AS PROTECTED FROM PHYSICAL DAMAGE. 5. MAX 15 AMP. N 14 GU WIRE (CHECK) 6. CONNECT G.E.C TO LUG ON NEUTRAL BUS |