Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE A LISTED GUY KIT OR STIFF ARM FOR MAST SUPPORT. 2. STRUT FOR MAST NOT SECURE TO STRUCTURE, AC ALSO 3. STRUT CLAMP LOOSE 4. MEYERS HUB ON TOP OF SERVICE NOT FLUSH/RAINTIGHT. 5. STRAP EMT WITHIN 3' OF J-BOX 6. TERMINATE CATV GROUND PROPERLY ON GROUND BAR OR LISTED CONNECTOR. 7. ADD NEW AC TO PERMIT. 8. EXPOSE GROUND RODS. 9. SEAL ROOF PENETRATIONS. 10. REMOVE PAINT UNDER GAS BOND & TIGHTEN CLAMP ALSO, SECURE BOND CONDUCTOR TO STRUCTURE BETTER. |
|
| 08/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PLEASE REMOVE BIRD THAT IS PROTECTING HER EGGS ON TOP OF SERVICE THEN CALL FOR INSPECTION. BIRD IS NOT IN THE MOOD FOR THIS INSPECTION AT THIS TIME |