Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/26/2006 | ELECTRIC - FINAL | Approved | ||
| 11/20/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IN J-BOX, EQUIPMENT GROUND TO BE SIZED FOR LARGEST OVER CURRENT DEVICE-NEC 250.122 (C) 2) TIGHTEN ALL FITTINGS 358.42 3) RACEWAYS ENTERING RAIN TITE ENCLOSURES NEED MYERS TYPE HUB OR SEALING LOCKNUT NEC 312.2 4) INDENTIFY PANEL DIRECTORYS NEC 408.4 5) YELLOW NOT TO BE USED AS NEUTRAL NEC 206.A 6) SEAL UNUSED OPENINGS IN ALL EQUIPMENT NEC 110.12A 7) USE PROPER BOLTS AT SERVICE SECTIONS |
|
| 10/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SEE T06EL00900 |