Permit: T06EL00907

Parcel: 123021150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/26/2006 ELECTRIC - FINAL Approved
11/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) IN J-BOX, EQUIPMENT GROUND TO BE SIZED FOR LARGEST OVER CURRENT DEVICE-NEC 250.122 (C)
2) TIGHTEN ALL FITTINGS 358.42
3) RACEWAYS ENTERING RAIN TITE ENCLOSURES NEED MYERS TYPE HUB OR SEALING LOCKNUT NEC 312.2
4) INDENTIFY PANEL DIRECTORYS NEC 408.4
5) YELLOW NOT TO BE USED AS NEUTRAL NEC 206.A
6) SEAL UNUSED OPENINGS IN ALL EQUIPMENT NEC 110.12A
7) USE PROPER BOLTS AT SERVICE SECTIONS
10/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SEE T06EL00900