Permit: T06EL00900

Parcel: 123021140

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/20/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SERVICE INSPECTION ONLY
1. PROPERLY TERMINATE SERVICE CONDUCTORS IN SERVICE DISCONNECT.
2. ROUTE GROUNDING ELECTRODE CONDUCTOR TO SERVICE DISCONNECT ENCLOSURE AND TERMINATE ON NEUTRAL BLOCK.
3. REMOVE GROUND JUMPERS BETWEEN SECTIONS SO YOU CAN PROPERLY TERMINATE EQUIPMENT GROUNDS.
4. INSTALL BREAKER BLANKS AS NEEDED.
5. REMOVE BONDING SCREWS FROM ALL SUB-PANELS.
6. IDENTIFY (BETTER) SERVICE NEUTRALS (OUT OF W.HEADS)
7. HAVE AN APPROVED SET OF PLANS ON SITE AND CHECK CALCULATIONS FOR SERVICE SIZE. IT (THE CALC'S) DO NOT APPEAR TO BE CORRECT.
8. HAVE ALL EQUIPMENT OPEN FOR INSPECTION.