Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY 2ND GROUND ROD. 2. WHERE IS GAS BOND? 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR ENTIRE EXPOSED LENGTH. 4. GROUNDING CONDUCTOR TO BE SIZED PER 250.112 5. PROTECT EMT CONDUIT FROM CORROSION WITH CONTACT OF SOIL 300.6 6. PROTECT CONDUCTORS AT FITTING 300.4 7. PLEASE PROVIDE A LADDER TO VERIFY JUNCTION BOX BONDING. |