Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999$ * METER IS TOO HIGH (6'3" MAX PER T.E.P) * CONDUIT - RISER IS SECURED TO UNTREATED WOOD (PLEASE REPLACE WITH SOMETHING THAT WILL HOLD UP FOR YEARS TO COME. SUCH AS UNISTRUT ETC.) * INSTALL LOCKNUT BETWEEN LB-PANEL CONNECTION (CHASE NIPPLES ARE NOT ALLOWED TO BE THE CONDUIT BOND CONNECTION POINT. * INSTALL STEALING LOCKNUT AT CONDUIT ENTRY AT TOP OF PANEL. |