Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 05/18/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT RISER CONDUIT WITHIN 3' OF PANEL, USE 1/4" BOLTS MIN. 2. INSTALL ROOF JACK 3. MAGIC MARKER NOT ACCEPTABLE FOR ADDRESS LABEL USE LABEL PERMANENTLY INSTALLED WITH SCREWS OR RIVETS. 4. CHASE NIPPLE NOT APPROVED AT LB TERMINATION, USE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS. 5. WHERE DID YOU SPLICE NEW WIRING TO EXISTING? USE APPROVED BOX. 6. SCRAP OFF PAINT ON GAS PIPING FOR CLAMP CONNECTION. 7. PERMIT REQUIRED FOR NEW AC SYSTEM. |
|
| 05/17/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* RECALL INSPECTION |