Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEUTRAL NEEDS TO BOND TO PANEL ENCLOSURE. 2. TIGHTEN BOND CLAMP SET SCREWS. 3. BURY OR SECURE TO STRUCTURE THE GROUNDING ELECTRODE CONDUCTOR. |
|
| 05/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND SERVICE NIPPLE. 2. BOND NEUTRAL TO PANEL ENCLOSURE (MAIN BONDING JUMPER OR SCREW). 3. INSTALL GROUND RODS AND BOND WATER AND GAS PIPES TO SERVICE. 4. USE INHIBITOR ON ALUMINUM CONNECTIONS. 5. IDENTIFY SERVICE DISCONNECT. |
|
| 05/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL LOCKED - REMOVE LOCK - RECALL INSPECTINO SEE NOTE AT BOTTOM OF YELLOW PERMIT CARD - NO APPOINTMENTS AT THIS TIME DUE TO WORK LOAD. 2. EXPOSE GROUND RODS, VERIFY WATER & GAS PIPE BONDING |