Permit: T06EL00844

Parcel: 107160140


Addresses:

2655 N GERONIMO AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. NEUTRAL NEEDS TO BOND TO PANEL ENCLOSURE.
2. TIGHTEN BOND CLAMP SET SCREWS.
3. BURY OR SECURE TO STRUCTURE THE GROUNDING ELECTRODE CONDUCTOR.
05/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. BOND SERVICE NIPPLE.
2. BOND NEUTRAL TO PANEL ENCLOSURE (MAIN BONDING JUMPER OR SCREW).
3. INSTALL GROUND RODS AND BOND WATER AND GAS PIPES TO SERVICE.
4. USE INHIBITOR ON ALUMINUM CONNECTIONS.
5. IDENTIFY SERVICE DISCONNECT.
05/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL LOCKED - REMOVE LOCK - RECALL INSPECTINO SEE NOTE AT BOTTOM OF YELLOW PERMIT CARD - NO APPOINTMENTS AT THIS TIME DUE TO WORK LOAD.
2. EXPOSE GROUND RODS, VERIFY WATER & GAS PIPE BONDING