06/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE BOND TO INTERIOR SIDE OF DIE ELECTRIC UNION FOR WATER BOND AND INTERIOR SIDE OF METER GAS
2. RECEPTACLE COVER TO BE AS PER 408.6
3. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT.
4. TIGHTEN GROUND STRAIN RELIEF.
5. IDENTIFY NEUTRAL CONDUCTOR.
6. A GUY BACK BRACE MAY BE NEEDED.