Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/12/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE BOND TO INTERIOR SIDE OF DIE ELECTRIC UNION FOR WATER BOND AND INTERIOR SIDE OF METER GAS 2. RECEPTACLE COVER TO BE AS PER 408.6 3. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT. 4. TIGHTEN GROUND STRAIN RELIEF. 5. IDENTIFY NEUTRAL CONDUCTOR. 6. A GUY BACK BRACE MAY BE NEEDED. |