Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2006 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 05/23/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/02/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GREEN WIRE USED AS HOT ON 30 AMP CIRCUIT WRONG USE BLACK. 2. SEAL HOLE BOTTOM OF SERVICE. 3. #14 WIRE ON 20 AMP BREAKERS SHOULD BE 15 AMP. 4. USED IMPROPER FITTING ON LB'S ENTERING EXCEPT NEW ONE. 5. 1/2" LB ON TOP OF SERVICE MISSING COVER. 6. WHEN RELOCATING A SERVICE - NEW GROUNDING SYSTEM REQUIRED CONSISTING OF 2 GROUND RODS 6' APART INCLUDING A WATER AND GAS BOND. 7. DRYER CIRCUIT USING TWO WHITE #10'S 8. ROOF JACK REQUIRED WHERE 2" GOES THRU ROOF. 9. ALL BREAKERS SHOULD BE ON A CHALLENGER TYPE. 10. NEUTRAL COMING OUT OF WEATHER HEAD TO BE TAPED WHITE. ONCE YOU RELOCATE SERVICE YOU ASSUME RESPONSIBILITY OF BRINGING IT UP TO CURRENT CODE STANDARDS. |