Permit: T06EL00823

Parcel: 116172330


Addresses:

1026 W COLORADO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
06/21/2006 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
05/23/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/02/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GREEN WIRE USED AS HOT ON 30 AMP CIRCUIT WRONG
USE BLACK.
2. SEAL HOLE BOTTOM OF SERVICE.
3. #14 WIRE ON 20 AMP BREAKERS SHOULD BE 15 AMP.
4. USED IMPROPER FITTING ON LB'S ENTERING EXCEPT NEW ONE.
5. 1/2" LB ON TOP OF SERVICE MISSING COVER.
6. WHEN RELOCATING A SERVICE - NEW GROUNDING SYSTEM REQUIRED CONSISTING OF 2 GROUND RODS 6' APART INCLUDING A WATER AND GAS BOND.
7. DRYER CIRCUIT USING TWO WHITE #10'S
8. ROOF JACK REQUIRED WHERE 2" GOES THRU ROOF.
9. ALL BREAKERS SHOULD BE ON A CHALLENGER TYPE.
10. NEUTRAL COMING OUT OF WEATHER HEAD TO BE TAPED WHITE.
ONCE YOU RELOCATE SERVICE YOU ASSUME RESPONSIBILITY OF BRINGING IT UP TO CURRENT CODE STANDARDS.