Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. COULD NOT LOCATE WATER/GAS BOND |
|
| 05/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* OCCUPANT UNABLE TO MEET TO OPEN -- WILL RESCHEDULE 11:15 AM |
|
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATE IS LOCKED FROM INSIDE BOTTOM PLEASE RECALL & LEAVE MESSAGE |
|
| 05/05/2006 | ELECTRIC - FINAL | Denied | 1. NEED WATER & GAS BOND - MAYBE IN HOUSE? 2. ONLY BREAKERS BY GE (GENERAL ELECTRIC) ALLOWED IN PANEL. 3. NEED TO USE PROPER FITTINGS AT OUTSIDE CONDUIT USE (WEATHERPROOF) TYPE. 4. SUPPORT CONDUIT. 5. WHITE CONDUCTOR ON 30 AMP CB TO BE BLACK, TAPE OK WHITE CONDUCTOR ON 50 AMP CB TO BE BLACK, TAPE OK |