Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL00794

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2006 ELECTRIC - INTERMEDIATE Approved
04/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE CONDUCTORS NEED TO BE SUNLIGHT RESISTANT NEC 310.8(D)
2. MAST NEEDS TO BE BONDED NEC 250.92
3. SERVICE GUTTER NEEDS TO BE BONDED NEC 250.92
*NOTE* THIS TYPE OF MYERS HUB NOT APPROVED FOR SERVICE SIDE BONDING - NEC 250.92(B)
4. BOND GAS PIPE TO SERVICE - NEC 250.104(B)
5. SERVICE 825 BLOCK 827'S PANEL COVERING FROM OPENING TO 90 DEGREES.
6. IF SEPARATE PIPE SYSTEMS (I.E. WATER & GAS) MAKE SURE ALL ARE BONDED TO SERVICE - NEC 250.104