Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00793
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR -- CALLED TEP 12:35 PM |
|
| 10/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND SERVICE RISER -- NEC 250.92 2. BOND SERVICE TERMINATION ENCLOSURE -- NEC 250.92 3. BONDING CONDUCTORS TO BE PROPERLY SIZED -- NEC 250.102 4. DRIVE GROUND RODS FLUSH -- NEC 250.53 5. REMOVE PAINT UNDER BOND LUGS OR CLAMPS -- NEC 250.112 6. SECURE TO STRUCTURE OR BURY MINIMUM 12" ALL BONDING AND GROUNDING ELECTRODE CONDUCTORS -- NEC 250.64 PROVIDE ACCESS TO INTERIOR OF UNITS FOR INSPECTION PARTIAL INSPECTION, FOR SERVICE ONLY. |