Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06EL00793

Parcel: 121061140


Addresses:

5804 E FAIRMOUNT ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00793

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK TO CLEAR -- CALLED TEP 12:35 PM
10/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. BOND SERVICE RISER -- NEC 250.92
2. BOND SERVICE TERMINATION ENCLOSURE -- NEC 250.92
3. BONDING CONDUCTORS TO BE PROPERLY SIZED --
NEC 250.102
4. DRIVE GROUND RODS FLUSH -- NEC 250.53
5. REMOVE PAINT UNDER BOND LUGS OR CLAMPS --
NEC 250.112
6. SECURE TO STRUCTURE OR BURY MINIMUM 12" ALL BONDING AND GROUNDING ELECTRODE CONDUCTORS --
NEC 250.64

PROVIDE ACCESS TO INTERIOR OF UNITS FOR INSPECTION
PARTIAL INSPECTION, FOR SERVICE ONLY.