Permit: T06EL00780

Parcel: 140151510


Addresses:

2236 E MINORKA ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/25/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
05/12/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE #2 NOT CORRECTED
DO NOT CALL FOR INSPECTION UNTIL DONE OR INSPECTION FEE WILL ASSESSED.
05/04/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE: #2 NOT CORRECTED -- CONDUIT MUST TERMINATE INTO A EMT CONNECTOR AT BOX.
04/28/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SET SCREW CONNECTOR COMING INTO LB IS NOT WEATHERPROOF - MUST BE COMPRESSION TYPE.
2. CONDUIT COMING INTO OUTSIDE LIGHT AT SW CORNER NEEDS TO PROPERLY GO INTO BACK OF BOX.
04/26/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING FOR MOTION SENSOR LIGHT NOT PER CODE
CONNECTED INTO PORCH LIGHT FRONT & BACK.
2. SUPPORT 1/2" CONDUIT ABOVE SERVICE & USE APPROVED FITTING TO SEAL OUT RAIN WATER.