Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T06EL00780
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
05/12/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE #2 NOT CORRECTED DO NOT CALL FOR INSPECTION UNTIL DONE OR INSPECTION FEE WILL ASSESSED. |
|
05/04/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: #2 NOT CORRECTED -- CONDUIT MUST TERMINATE INTO A EMT CONNECTOR AT BOX. |
|
04/28/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SET SCREW CONNECTOR COMING INTO LB IS NOT WEATHERPROOF - MUST BE COMPRESSION TYPE. 2. CONDUIT COMING INTO OUTSIDE LIGHT AT SW CORNER NEEDS TO PROPERLY GO INTO BACK OF BOX. |
|
04/26/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING FOR MOTION SENSOR LIGHT NOT PER CODE CONNECTED INTO PORCH LIGHT FRONT & BACK. 2. SUPPORT 1/2" CONDUIT ABOVE SERVICE & USE APPROVED FITTING TO SEAL OUT RAIN WATER. |