Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00776

Parcel: 122091370


Addresses:

4241 E PIMA ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO FURTHER WORK UNTIL QUALIFIED CONTRACTOR CONTACTS CITY TO VERIFY WORK.
04/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SUB-PANEL NEED CKTS IDENTIFIED.
2. SUB-PANEL HAS OPEN BREAKER SPACES.
3. SUB-PANEL FEEDER INSULATION IS REMOVED FROM CONDUCTORS.
4. MAX. 15 AMP. BREAKER FOR 14 GA. WIRE
5. GROUND FEEDER J-BOX AND INSTALL COVER.
6. CONDUCTORS ENTERING ENCLOSURES NEED PROPER CONNECTOR.
7. PROVIDE MAST SUPPORT TO STRUCTURE.
8. NEED 2" MINIMUM MAST.
9. SUB-PANEL FEEDER NEEDS COMMON TRIP BREAKER.
10. TIGHTEN ALL CONNECTIONS, SET SCREWS, ETC.
11. IDENTIFY CKTS AT SERVICE.
12. BOND ALL METAL PIPING TO SERVICE - INCLUDING WAST PIPE IN UTILITY.
NEED QUALIFIED ELECTRICAL CONTRACTOR.