Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NO FURTHER WORK UNTIL QUALIFIED CONTRACTOR CONTACTS CITY TO VERIFY WORK. |
|
| 04/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SUB-PANEL NEED CKTS IDENTIFIED. 2. SUB-PANEL HAS OPEN BREAKER SPACES. 3. SUB-PANEL FEEDER INSULATION IS REMOVED FROM CONDUCTORS. 4. MAX. 15 AMP. BREAKER FOR 14 GA. WIRE 5. GROUND FEEDER J-BOX AND INSTALL COVER. 6. CONDUCTORS ENTERING ENCLOSURES NEED PROPER CONNECTOR. 7. PROVIDE MAST SUPPORT TO STRUCTURE. 8. NEED 2" MINIMUM MAST. 9. SUB-PANEL FEEDER NEEDS COMMON TRIP BREAKER. 10. TIGHTEN ALL CONNECTIONS, SET SCREWS, ETC. 11. IDENTIFY CKTS AT SERVICE. 12. BOND ALL METAL PIPING TO SERVICE - INCLUDING WAST PIPE IN UTILITY. NEED QUALIFIED ELECTRICAL CONTRACTOR. |