Permit: T06EL00771

Parcel: 128062100


Addresses:

6014 E BEVERLY ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RE-ROUTE COOLER WATER LINES IN FRONT OF SERVICES.
2. PATCH HOLE AT BOTTOM OF GUTTER BY OFFSET NIPPLE.
3. DO NOT USE PANEL GROUND BAR AS A SPLICING MEANS TO CONNECT GROUNDING ELECTRODE CONDUCTOR TO #6016 SERVICE, A SPLIT BOLT TAP IS ALLOWED OUTSIDE OF PANEL ENCLOSURE.
4. GAS BONDING NOT APPROVED AT GAS METERS INSTALL CONTINUOUS BOND WIRE TO SERVICE.
5. VERIFY WATER BOND TO BOTH UNITS.