Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RE-ROUTE COOLER WATER LINES IN FRONT OF SERVICES. 2. PATCH HOLE AT BOTTOM OF GUTTER BY OFFSET NIPPLE. 3. DO NOT USE PANEL GROUND BAR AS A SPLICING MEANS TO CONNECT GROUNDING ELECTRODE CONDUCTOR TO #6016 SERVICE, A SPLIT BOLT TAP IS ALLOWED OUTSIDE OF PANEL ENCLOSURE. 4. GAS BONDING NOT APPROVED AT GAS METERS INSTALL CONTINUOUS BOND WIRE TO SERVICE. 5. VERIFY WATER BOND TO BOTH UNITS. |