Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* ALL PREVIOUS CORRECTIONS HAVE BEEN COMPLETED. |
|
| 05/05/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK ITEMS 1, 2 & 3 OF INSPECTION EARLIER TODAY 2) RECEIVED CHECK #1226 FOR $108.00 AFTER HOURS INSPECTION |
|
| 05/05/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT ENTER THRU TOP OF SQ. D SERVICE AS PER INSTRUCTIONS. 2. WATER FAUCET OUT IN FRONT OF SERVICE VIOLATES CLEARANCE REQUIREMENTS OF NEC 2002 CELAR DOWN TO GRADE & 36" OUT. 3. GROUND ROD CLAMPS TO HAVE WIRE OPPOSITE SIDE OF BOLT. 4. WILL NEED 15 AMP. CB'S ON 14 WIRE CIRCUITS. 5. WILL NEED 30 AMP. CB'S ON 10 WIRE CIRCUITS. |