Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) IDENIFY NEUTRAL CONDCUCTOR WITH WHITE TAPE 2) PLEASE RECALL AFTER CROSS OVER |
|
| 05/02/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. BOND RISER. 2. TERMINATE GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL. 3. A NEUTRAL IS NEEDED TO INTERIOR DISCONNECT. 4. PLEASE TIGHTEN LOCKNUT. 5. A GAS AND WATER BOND IS NEEDED. |