Permit: T06EL00766

Parcel: 106010520


Addresses:

441 E KNOX DR

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) HOSE BIB TO BE MOVED AND RELOCATED TO PROVIDE BETTER CLEARANCE IN FRONT OF SERVICE
05/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL INSTRUCTIONS FOR SD ALL IN ONE RESTRICT ENTRY OF LOAD CONDUCTORS THRU TOP WALL SEE LISTINGS IN COVER.
2. WATER AND GAS BOND MISSING.
3. WATER FAUCET AT BASE 4 PAENL ON FLOOR INFRINGE ON CLEARANCE REQUIRED BY NEC 2002 110-26 ITS ALSO A TRIP HAZARD IN FRONT OF SERVICE.
4. HOT LEG ON POOL PUMP TO BE TAPED BLACK.
05/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
GATE LOCKED