Permit: T06EL00759


Addresses:

3125 N GERONIMO AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE DISCONNECT ON BACK NEEDS MARKED AS SERVICE DISCONNECT, BRANCH CKTS IDENTIFIED AND HOLD DOWN KIT FOR BACK FED MAIN BREAKER I DID NOT SEE THIS DISCONNECT LAST INSPECTION.
06/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. IDENTIFY ALL SERVICE DISCONNECTS AS "SERVICE DISCONNECT" NEC 230.70 (B)
2. BONDING CONDUCTOR TO SERVICE GUTTER AND SERVICE MAST IS UNDERSIZED NEC 250.102(C)
06/07/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND MAST AND SERVICE RACEWAYS
2) IDENTIFY SERVICE DISCONNECTS
3) CALL FOR FINAL