Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. METER BASE IS NOT TO EXCEED 6'3" TO CENTER PER T.E.P 2. SECURE RISER BELOW ROOF PER NEC & TEP 3. EXPOSE GROUND ROOF. 4. SHEATH OR CABLES NEED TO BE INSIDE PANEL (EXPOSED THW CONDUCTORS ARE SHOWING BEHIND PANEL. 5. MAIN BREAKER TOO HIGH. |