Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL00747
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 05/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRIVE RODS FLUSH OR BELOW FINISHED GRADE. 2. BOND GAS TO SERVICE (WATER PIPING IS NON-METALLIC MAKE PERMANENT NOTE AT SERVICE PANEL) 3. E.M.T CONNECTOR AT LB IS NOT ACCEPTABLE PER 110-3 N.E.C (FOR PANEL CONNECTION). 4. INSTALL FHA STRAPS ABOVE ELECTRICAL PANEL. 5. INSTALL PROPER STAPLES FOR SECURING ROMEX AT PANEL |
|
| 05/03/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* |