Permit: T06EL00747

Parcel: 112061470


Addresses:

2237 E MITCHELL ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL00747

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/17/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
05/16/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DRIVE RODS FLUSH OR BELOW FINISHED GRADE.
2. BOND GAS TO SERVICE (WATER PIPING IS NON-METALLIC MAKE PERMANENT NOTE AT SERVICE PANEL)
3. E.M.T CONNECTOR AT LB IS NOT ACCEPTABLE
PER 110-3 N.E.C (FOR PANEL CONNECTION).
4. INSTALL FHA STRAPS ABOVE ELECTRICAL PANEL.
5. INSTALL PROPER STAPLES FOR SECURING ROMEX AT PANEL
05/03/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*