Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE HOME DAVE 919-5150 |
|
| 04/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH. NOT GREED TAPED WHITE. 2. BLUE WIRE NUT ONLY LISTED FOR 2 CONDUCTORS LARGER THAN #8 3. GROUNDING EQUIPMENT CONDUCTORS NOT TO BE DOUBLED TO ONE. 4. PLEASE IDENTIFY CIRCUITS FOR CONDUCTORS IN JUNCTION BOXES TO VERIFY PHASING FOR NEUTRAL LOADS. 5. CANNOT PARALLEL CONDUCTOR SMALLER THAN 1/0 |