Permit: T06EL00745

Parcel: 11008008C


Addresses:

2732 N ORCHARD AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE HOME
DAVE 919-5150
04/21/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH. NOT GREED TAPED WHITE.
2. BLUE WIRE NUT ONLY LISTED FOR 2 CONDUCTORS LARGER THAN #8
3. GROUNDING EQUIPMENT CONDUCTORS NOT TO BE DOUBLED TO ONE.
4. PLEASE IDENTIFY CIRCUITS FOR CONDUCTORS IN JUNCTION BOXES TO VERIFY PHASING FOR NEUTRAL LOADS.
5. CANNOT PARALLEL CONDUCTOR SMALLER THAN 1/0