Permit: T06EL00741

Parcel: 129040990


Addresses:

1916 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. NEED ELECTRICAL CONTRACTOR (LICENSED) DOING WORK.
2. CONDUCTORS IN RACEWAYS NEED TO BE DERATED --
NEC 310.15 (B)(2)
3. NEED ACCESS TO INTERIOR BRANCH CKT J-BOX
4. TOP OF SERVICE HUB COVER NOT SECURE
*NOTE: PARTIAL INSPECTION ONLY AT THIS TIME.
05/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NOTES:
1. CHASE NIPPLE NOT ALLOWED FOR LB TERMINATION AT BOTTOM OF PANEL. USE CLOSE NIPPLE WITH LOCKNUTS & BUSHING. LB COVER MISSING.
2. W/P J-BOX ON ROOF, MUST BE MTD UPRIGHT
05/09/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*