Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEED ELECTRICAL CONTRACTOR (LICENSED) DOING WORK. 2. CONDUCTORS IN RACEWAYS NEED TO BE DERATED -- NEC 310.15 (B)(2) 3. NEED ACCESS TO INTERIOR BRANCH CKT J-BOX 4. TOP OF SERVICE HUB COVER NOT SECURE *NOTE: PARTIAL INSPECTION ONLY AT THIS TIME. |
|
| 05/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1. CHASE NIPPLE NOT ALLOWED FOR LB TERMINATION AT BOTTOM OF PANEL. USE CLOSE NIPPLE WITH LOCKNUTS & BUSHING. LB COVER MISSING. 2. W/P J-BOX ON ROOF, MUST BE MTD UPRIGHT |
|
| 05/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |