Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL00738

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/03/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL
USE METAL BOXES FOR MC TERMINATION
06/22/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
TERMINATE MC IN METAL BOXES
06/15/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SIZE J-BOXES PER TABLE 314.16 (A)
#12 NEEDS MIN. 2.25 CUBIC INCHES
PER CONDUCTOR AND THE DEVICE (RECEPTACLE COUNTS AS 2 CONDUCTORS 314.16 (B) 4
2. SECURE MC CABLE WITHIN 12" OF J-BOXES
3. USE APPROVED MC CONNECTORS.
4. REMOVE UNUSED CONNECTORS & SEAL OPENING WITH K.O SEAL.
05/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*