Permit: T06EL00725

Parcel: 129091210


Addresses:

1520 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/25/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/24/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THIS PERMIT BELONGS TO A GENERAL INSPECTOR BECAUSE OF T06CM02323 -- CALLED OFFICE TO NOTIFY.
05/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. THIS PERMIT IS FOR UPGRADE & RECEPT. THE INSIDE OF HOUSE IS REWIRED & COVERED.
2. ADD ELECTRICAL WORK TO T06CM02323 FOR INTERIOR WIRING, PROVIDE PLAN. SEE NOTES PREVIOUS INSPECTION.
05/12/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. AN ADDRESS LABEL IS NEEDED.
2. PLEASE EXPOSE GROUND RODS.
3. MISSING LB COVER
4. PLEASE VERIFY GAS & WATER BONDING.
5. THIS SERVICE TO BE RELEASED BY COMBINATION INSPECTOR.
DOING INTERIOR REMODEL
6. PROTECT CONDUCTORS FROM DAMAGE OF SCREW IN
BOXES 314.70
7. WE HAVE CONDUCTOR BOX OVERFILL.
8. IDENTIFY UNGROUNDED CONDUCTOR PER 200.7
9. PLEASE PROVIDE GROUND SPLICE TERMINATIONS.
10. BOX CLAMP NOT TO BE BROKEN OUT. CABLES TO SECURE TO BOX 312.5
11. VERIFY 2 SMALL APPLIANCE CIRCUITS IN KITCHEN 210.52
12. BATHROOM GFI TO BE PER 210.8 & 210.52
13. USE GROUND SCREW IN LIGHT BOXES.
14. PROVIDE GROUND TAIL FOR SWITCHES AT ROUGH-IN