Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00711
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ROD CLAMPS NEED TO BE BRASS. 2. WATER & GAS BOND TO BE ATTACHED. 3. BOARD SUPPORTING 2" CLAMP BELOW ROOF NEEDS TO BE SCREWED IN. 4. INSTALL ROOF JACK - CAN BE LEFT UP UNTIL ROOF REPAIRED. 5. USE GROUND BAR IN J-BOX TO TIE ALL GROUNDS TO METAL 6. SEAL HOLE BOTTOM OF J-BOX 7. USE APPROVED LISTED CLAMPS FLEX GOING INTO ATTIC NOT PLUMBING TAPE. |
|
04/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR INCREASE. TIE WATER BOND SEPARATELY TO #4 GOING TO SERVICE. |
|
04/27/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |