Permit: T06EL00707

Parcel: 123040050


Addresses:

3006 E LESTER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) NEC 2002 230.54 C-EXCEPTION ALLOWS POA TO BE W/IN 2' ABOVE WEATHERHEAD
2) NEC 2002 09-B-NOT COVERED BY NEC-B5 SERVICE DROPS PER UTILITY
08/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. MOVE SERVICE TERMINALS TO LINE POSITION FOR OVERHEAD FEED SEE MANUFACTURER NOTE IN METER SECTION NEC 110
2. MUST HAVE MINIMUM 10' CLEARANCE FROM GRADE FOR SERVICE CONDUCTORS NEC 230
3. SERVICE DROP CAN'T ATTACH ABOVE WEATHERHEAD
NEC 230