Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NEC 2002 230.54 C-EXCEPTION ALLOWS POA TO BE W/IN 2' ABOVE WEATHERHEAD 2) NEC 2002 09-B-NOT COVERED BY NEC-B5 SERVICE DROPS PER UTILITY |
|
| 08/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MOVE SERVICE TERMINALS TO LINE POSITION FOR OVERHEAD FEED SEE MANUFACTURER NOTE IN METER SECTION NEC 110 2. MUST HAVE MINIMUM 10' CLEARANCE FROM GRADE FOR SERVICE CONDUCTORS NEC 230 3. SERVICE DROP CAN'T ATTACH ABOVE WEATHERHEAD NEC 230 |