Permit: T06EL00707

Parcel: 123040050


Addresses:

3006 E LESTER ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
05/10/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
OK PVC UG
04/14/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO MORE THAN 4 90DEGREE BENDS IN RACEWAY.
2. NEED EQUIPMENT GROUND FOR SUB-PANEL.
3. MAKE SURE RACEWAYS ARE SOLIDLY CONNECTED.
4. MAKE SURE FEEDERS COMPLY WITH NEC 310.8 (C)
I COULD NOT READ MARKING ON CONDUCTOR.