Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* OK PVC UG |
|
| 04/14/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO MORE THAN 4 90DEGREE BENDS IN RACEWAY. 2. NEED EQUIPMENT GROUND FOR SUB-PANEL. 3. MAKE SURE RACEWAYS ARE SOLIDLY CONNECTED. 4. MAKE SURE FEEDERS COMPLY WITH NEC 310.8 (C) I COULD NOT READ MARKING ON CONDUCTOR. |