Permit: T06EL00695

Parcel: 122162510

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 50 AMP BREAKER TO HOUSE SHOULD BE 20 AMP.
2. GROUND WIRE IN PANEL AREA NOT TERMINATED
3. SECURE GROUND WIRE BELOW SERVICE
RECALL FOR INSPECTION.