Permit: T06EL00682

Parcel: 11009065C

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
04/19/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
04/14/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/12/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SMOKE DETECTOR MISSING, MUST BE INSTALLED AND OPERATIONAL.
2. INSIDE SUB-PANEL, CONDUIT WHICH BRINGS IN FEEDERS FROM SERVICE HAS PULLED OUT FROM ATTACHING TO PANEL MUST RE-ATTACH TO PANEL AND LOCK NUT INSTALLED.
3. SEAL LARGE HOLE IN SUB-PANEL & REPLACE SCREWS MISSING WHICH COVER IT.
4. EQUIPMENT GROUND COMING INTO SUBPANEL FROM SERVICE CANNOT TIE INTO NEUTRAL BAR THIS MAY TRANSFER CURRENT INTO EQUIPMENT GROUND - ISOLATE GREEN WIRE AND PROPERLY ATTACH TO GROUND.
5. 30 AMP - 240 VOLT RECEPTACLE BY GATE TO HAVE A WEATHERPROOF COVER SINCE OUTSIDE.