Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CABLE TO ENTER IN NON FLEXIBLE RACEWAY 2. SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 3. NM CABLE AMPACITY TO BE AS PER 330.80 4. USE APPROVED CONDUCTOR COLORS. 5. SECURELY ANCHOR CONDUIT STRAPS. 6. SEAL AND PROTECT CABLE ENTERING FROM BACK OF PANEL |