Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL00658
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
06/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CLAMPS/LUGS FOR DIRECT AND BURRIAL NEED TO BE LISTED FOR BURRIAL (GROUNDING ELECTRODE CONDCUTORS) |
|
05/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. GAS AND WATER PIPE BONDING CONDUCTOR IS UNDERSIZED NEC 250.104 2. NIPPLE FROM CT CAN TO GUTTER BONDING (AND GUTTER) CONDUCTOR IS UNDERSIZED NEC 250.102 (C) 3. MAST NEEDS TO BE BONDED NEC 250.92 AND SIZED PROPERLY NEC 250.102(C). 4. CT ENCLOSURE BONDING CONDUCTOR IS UNDERSIZED NEC 250.102 (C) |
|
05/26/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SIZE BONDING CONDUCTORS CORRECTLY |
|
05/16/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* JOB IN PROGRESS |
|
05/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CODE COMPLIANCE AND GENERAL REVIEW OF ELECTRICAL ON JOB. |