Permit: T06EL00658

Parcel: 115070750


Addresses:

1742 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL00658

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2006 ELECTRIC - INTERMEDIATE Approved
06/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CLAMPS/LUGS FOR DIRECT AND BURRIAL NEED TO BE LISTED FOR BURRIAL (GROUNDING ELECTRODE CONDCUTORS)
05/31/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. GAS AND WATER PIPE BONDING CONDUCTOR IS UNDERSIZED NEC 250.104
2. NIPPLE FROM CT CAN TO GUTTER BONDING (AND GUTTER) CONDUCTOR IS UNDERSIZED NEC 250.102 (C)
3. MAST NEEDS TO BE BONDED NEC 250.92 AND SIZED PROPERLY NEC 250.102(C).
4. CT ENCLOSURE BONDING CONDUCTOR IS UNDERSIZED NEC 250.102 (C)
05/26/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
SIZE BONDING CONDUCTORS CORRECTLY
05/16/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
JOB IN PROGRESS
05/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CODE COMPLIANCE AND GENERAL REVIEW OF ELECTRICAL ON JOB.