Permit: T06EL00645

Parcel: 13401025B


Addresses:

350 S BROWN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE NEEDS TO BE UPGRADED TO HANDLE THE 60 AMPS OF ADDED LOAD AND TO CLEAR UP THE IMPROPER TAPS AT THE 100 AMP MAIN DISCONNECT SWITCH.
2. INSTALL GFCI RECEPTACLES AT BACK PORCH & WEATHERPROOF COVERS ARE REQUIRED.
3. ROOM AT CARPORT BREEZEWAY HAS EXPOSED CONDUCTORS AS DOES WEST EXTERIOR J-BOX.
4. ALL GROUNDING TYPE RECEPTACLES THROUGHOUT THE HOUSE NEED TO BE PROPERLY GROUNDED PER N.E.C OR GFCI PROTECTED OR THEY NEED TO BE REPLACED WITH NON-GROUNDING TYPE RECEPTACLES (2 WIRE).