Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. A.C BREAKER TOO LARGE FOR #8 COPPER CONDUCTOR (WRONG MAKE) 2. E.M.T CONDUIT NOT SUPPORTED (A.C. CONDUIT) 3. INSTALL BONDING BUSHING ON A.C. CONDUIT |
|
| 04/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |