Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00642
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY ALL PANEL DIRECTORIES 2. NEUTRALS AND GROUNDS TO BE SEPARATE IN SUB-PANEL 3. PANEL DOES NOT HAVE PROPER FRONT CLEARANCE 4. USE PROPER CONNECTORS FOR ROMEX INTO J-BOX 5. GROUND J-BOX 6. J-BOX TO BE ACCESSIBLE NOT SET BACK IN WALL 7. STAPLE ROMEX GOING INTO BOXES 8. ROMEX SHEATHING TO EXTEND INTO BOX 1/4" MINIMUM 9. SECURE/SUPPORT ROMEX IN CRAWL SPACE 10. NEED HOLDDOWN DEVICE FOR BACK FED MAIN BREAKER THERE WILL BE A REFEE IF NOT CORRECT NEXT TIME. |
|
06/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |