Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00642

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY ALL PANEL DIRECTORIES
2. NEUTRALS AND GROUNDS TO BE SEPARATE IN SUB-PANEL
3. PANEL DOES NOT HAVE PROPER FRONT CLEARANCE
4. USE PROPER CONNECTORS FOR ROMEX INTO J-BOX
5. GROUND J-BOX
6. J-BOX TO BE ACCESSIBLE NOT SET BACK IN WALL
7. STAPLE ROMEX GOING INTO BOXES
8. ROMEX SHEATHING TO EXTEND INTO BOX 1/4" MINIMUM
9. SECURE/SUPPORT ROMEX IN CRAWL SPACE
10. NEED HOLDDOWN DEVICE FOR BACK FED MAIN BREAKER

THERE WILL BE A REFEE IF NOT CORRECT NEXT TIME.
06/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*