Permit: T06EL00642

Parcel: 115041600


Addresses:

750 E MABEL ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06EL00642

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2007 ELECTRIC - UNDERGROUND Approved
06/08/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/10/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE 1ST GROUND ROD CLAMP IS OF A TYPE APPROVED ONLY FOR ABOVE GROUND - IT WILL CORRODE UNDERGROUND USE A TYPE AS ON 2ND ROD.
2. SINCE PVC PAINTED I CANNOT TELL IF IT IS SCHEDULE 80 - READ YOUR NOTE, SCH 80 IS THICKER PAINT WILL NOT OFFER PHYSICAL PROTECTION REQUIRED.
04/07/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING SYSTEM REQUIRED - 2 GROUND RODS 6' APART WITH AN UNSPLICED #4 COPPER, IN ADDITION WATER PIPING & GAS PIPING REQUIRED TO BE BONDED TO SERVICE. STRAP TO WALL.
2. CLOSE OF OPENING GROUND CONDUCTORS RUN INTO SERVICE .
3. ONLY SCH 80 PVC ALLOWED TO RUN OUTSIDE UNPROTECTED.