Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06EL00642
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2007 | ELECTRIC - UNDERGROUND | Approved | ||
06/08/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
04/10/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE 1ST GROUND ROD CLAMP IS OF A TYPE APPROVED ONLY FOR ABOVE GROUND - IT WILL CORRODE UNDERGROUND USE A TYPE AS ON 2ND ROD. 2. SINCE PVC PAINTED I CANNOT TELL IF IT IS SCHEDULE 80 - READ YOUR NOTE, SCH 80 IS THICKER PAINT WILL NOT OFFER PHYSICAL PROTECTION REQUIRED. |
|
04/07/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING SYSTEM REQUIRED - 2 GROUND RODS 6' APART WITH AN UNSPLICED #4 COPPER, IN ADDITION WATER PIPING & GAS PIPING REQUIRED TO BE BONDED TO SERVICE. STRAP TO WALL. 2. CLOSE OF OPENING GROUND CONDUCTORS RUN INTO SERVICE . 3. ONLY SCH 80 PVC ALLOWED TO RUN OUTSIDE UNPROTECTED. |