Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/13/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR SERVICE INCREASE. CALL FOR FINAL WHEN ALL BRANCH CIRCUITS HAVE BEEN COMPLETED |
|
| 04/06/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* *INSTALL 2 GROUND RODS (MIN. 6' APART) *INSTALL GROUNDING ELECTRODE CONDUCTOR WITHOUT SPLICE BETWEEN SERVICE AND GROUND RODS. *INSTALL #4 WATER BOND TO ELEC. SERVICE. *INSTALL #4 GAS BOND TO ELEC. SERVICE. *INSTALL RIGID OR IMC THREADED RISER FOR SERVICE RISER. *INSTALL METAL ADDRESS TAG PER T.E.P AND INTERNATIONAL RESIDENTIAL CODE. |